Rental Product details

Tan Delta Testing Kit

Tan Delta Testing Kit

  • Overview
  • Specification
  • Brochure

The M4100 is the industry standard for power apparatus and insulation testing. Its unique combination of test capabilities and artificial intelligence analysis software makes it the power industry’s most trusted Power Factor/Tan-Delta instrument. These instruments are used around the globe thanks to their comprehensive testing options, safety features and measurement accuracy.

  • Operating Temperature : -20° to 50°C / -4° to 122°F
  • Dry Heat :- IEC 60068-2-2
  • Cold :- IEC 60068-2-1
  • Shock & Vibration :- IEC 60068-2-27, IEC 60068-2-7 & ASTM D999.75
  • Drop Test :- EC 60068-2-6
  • Weight :- 95 lb / 43 kg
  • Dimensions :- 10.3 H x 20 W x 25.3 D (in) 26 H x 50.8 W x 64.1 D (cm)
  • Software :- DTA6 Basic
  • Power Input :- 95-264 VAC, Auto Sensing 47 to 63 Hz Accommodates Inverter and Portable Generators 16 A max at 110 V 10 A max at 220 V Accommodates GFIC/RCBO Class A & B
  • Field Verification & Calibration :- Integrated Self-Calibration & Verification Module 3 Resistive Standards Amplifier Test Range: 7-All Nominal Test Ranges Coverage:  Watts, Amps, PF/Tan-Delta, Internal Source Loss, HV Cable, LV Cable(s)
  • Safety Features :- Open Ground Detection Circuit Abnormal Current Sensing System with continuous temperature compensation Safety Switches: 2-Deadman Safety Strobe
  • Source Output :- 3 kVA 25 V to 12 kV Output Current: Continuous @ 100 mA at 10 kV 30 minutes @ 200 mA at 10 kV 4 minutes @ 300 mA at 10 kV
  • Power Factor/Tan-Delta Measurement :- Range: 0 to ±100.00% Resolution: 0.01% (0.0001) Typical Accuracy: ± 0.005%
  • Capacitance Measurement :- Range: 0 to 100 μF Resolution: 0.01 pF
  • Inductance Measurement :- Range: 6 H to 10 MH Resolution: 0.01 H
  • Watts Measurement :- Range: 0 to 2 kW, actual power Resolution: 0.5 mW